Audiovisual signaler WS-24-I
Siren and flashing light – Energy-buffered
Characteristics
- Includes both a siren and a flashing light
- The volume of the siren can be continuously adjusted via a potentiometer
- The frequency of the signaling can be adjusted between 0.5 Hz and 2 Hz via a potentiometer
- Bridging time of at least 4 minutes in the event of a power failure
- Depending on the operating conditions, the WS-24-I can signal triggered edges for 10 to 240 seconds or as long as the alarm input signal is present
- Optionally, a limit switch can be connected to switch the warning signal device on again when the door is briefly reopened
- Optional connection of a 24 V continuous supply or supply in parallel with the hold-open device (easy retrofitting) for existing gates is possible
Product details
Technical data
Input voltage | 24 V DC ± 10 % |
Signaling time from energy storage | min. 4 min |
Charging time (memory empty) | ca. 5 min |
Min. charging time until function | 35 s |
Dimensions | 84 mm x 82 mm x 55 mm |
Protection class | IP 54 |
Installation | Wall and ceiling installation |
Housing color | grey, similar to RAL 7035 |
Temperature range | +10 to +40 °C |
Noise level | 85 to 105 dB |
Options
- Includes both a siren and a flashing light
- The volume of the siren can be continuously adjusted via a potentiometer
- Flashing (50:50) or flashing (30:70) can be selected via a DIP switch
- The frequency of the signaling can be adjusted between 0.5 Hz and 2 Hz via a potentiometer
- Bridging time of at least 4 minutes in the event of a power failure
- The acoustic signaling device (siren) can be switched off via a jumper
- Depending on the operating conditions, the WS-24-I can signal triggered edges for 10 to 240 seconds or as long as the alarm input signal is present
- Optionally, a limit switch can be connected to switch the warning signal device on again when the door is briefly reopened
- Optional connection of a 24 V continuous supply or supply in parallel with the hold-open device (easy retrofitting) for existing gates is possible
Dimension of X: On overlapping doors the included plastic spacers (2 mm, 3 mm and 10 mm thick) compensate for a height difference of up to 15 mm between door leaf and frame.
More information on the dimensions of all mounting plates and brackets can be found under ‘Installation accessories’.
General information
From the perspective of the risk assessment based on product standard EN 16034 in conjunction with the Machinery Directive and from the perspective of the DGUV, standard EN 12604 “Doors – Mechanical aspects – Requirements and test methods” must be observed.
This stipulates that in the event of fire, the closing of vertical and horizontal curtains, doors and gates must be accompanied by an audible and visual warning signal if the closing speed exceeds 0.3 m/s or the force acting on the human body or body parts exceeds 200 N.
The signaling must also be guaranteed in the event of a power failure.
Order information
Order Information
Description | Part No. |
---|---|
Signaler energy-buffered WS-24-I, external siren-warning, with red LED flashing light | 700172 |
Downloads
File Name | Type |
---|---|
Documents | |
Catalog: Accessories for hold-open systems |