ATEX-proof electromagnets

Encapsulated, with connection cable, for hazardous zones 1 & 2, 21 & 22

Characteristics

  • They belong to group II of explosion-proof devices
  • Authorized for use in hazardous zones of classification 1 & 2, 21 & 22
  • Provided with different-lenght connection cables (indicated in the corresponding part number, other cable lengths available on demand)
  • As standard, equipped with diodes (spark extinction diodes) for suppressing the induced current on opening and with polarity protection
  • As counter piece for the electromagnet a counter plate has to be fixed on the door
  • Some articles may differ from the photo

Product details

Technical data

Voltage24 VDC +/-15 %
Temperature range-20 °C to +40 °C
Surfacezinc-plated steel
Remanence0 N
Duty cycle100 %
ProtectionIP 66
Electrical connectionconnection cable
Holding force EM GD 50 Ex..m600 N
Holding force EM GD 70 Ex..m1450 N
Power consumption EM GD 50 Ex..m67 mA (1,6 W)
Power consumption EM GD 70 Ex..m70 mA (1,7 W)
Marking according to ATEXEx II 2G Ex mb IIC T6 Gb or
Ex II 2D Ex mb IIIC T85°C Db

Certificates & approvals

  • Tested according to both EN 1155 and Directive 2014/34/EU (ATEX)
  • Type examination certificate IBExU14ATEX1211X/PTB 03 ATEX 2174 X

Dimensions

All dimensions in mm

Ex-proof electromagnet

Ex-Proof Electromagnets - Dimensions

Mounting plate for EM GD Ex with terminal box

Mounting Plate for EM GD Ex

Fuse for Ex-proof magnets, medium time lag, 200 mA

Fuse for Ex-Proof Magnets

All dimensions in mm

Installation

Installation notes

The explosion-proof magnet is mounted directly on the wall behind the door that needs to be kept open. For a safe installation we recommend our mounting plate, part no. 205252 (see ‘Dimensions’), to which the magnet is fixed with 2 M4 screws.

To protect the ex-proof magnets from a possible short circuit, a fuse, max. 3 x IB according to IEC 60127-2-1, corresponding to the rated current of the magnet has to be connected upstream to the magnet (G fuse 200 mA type M). On the casing is provided a terminal for the connection of the equipotential bonding with a minimum cross section of 4 mm².

You can find more installation information under ‘Downloads’.

Fuse / Fuse carrier for explosion-proof magnets

The fuse carrier with the prescribed fuse is placed directly into the feeding line to the ex-proof magnet. There are available two different types of fuse carriers:

  • Fuse carrier for solding directly into the feeding line, with bayonet catch. Dimensions of the fuse carrier: L = 43,2 mm, Ø 14,2 mm (suitable for cables with a cross section of max. 4 mm) (part no. 040587)

Fuse-carrier-040587

  • Fuse carrier for mounting on top hat rails, with pivoting retaining bracket (part no. 040588)

Elektro-Haftmagnet EX-Bereich Montage 2

Advice:

  • According to fire protection regulations, a switch has to be installed next to the fire door to release the electromagnet (ex-proof hand switch, part no. 700232).
  • If the switch is connected within the hazardous area, the connection cable has to be connected in a casing which corresponds to the demands of an acknowledged ignition protection type in accordance with EN 50014, section 1.2. During installation and connection, all relevant regulations for hazardous areas have to be observed.

Order information

Order Information

DescriptionPart No.
EM GD 50 Ex 30 m electromagnet, 600 N, 24 VDC, with 15 m connection cable, II 2G Ex mb IIC T6 Gb/II 2D Ex mb IIIC T85°C Db, LE 07016040154-15
EM GD 50 Ex 30 m electromagnet, 600 N, 24 VDC, with 5 m of ex-certified connection cable, II 2G Ex mb IIC T6 Gb/II 2D Ex mb IIIC T85°C Db, LE 07016040154-05
EM GD 70 Ex 43 m electromagnet, 1450 N, 24 VDC, with 2 m connection cable,II 2G Ex mb IIC T6 Gb/II 2D Ex mb IIIC T85°C Db, LE 07016040156
EM GD 70 Ex 43 m electromagnet, 1450 N, 24 VDC, with 5 m connection cable, II 2G Ex mb IIC T6 Gb/II 2D Ex mb IIIC T85°C Db, LE 07016040156-05
EM GD 70 Ex 43 m electromagnet, 1450 N, 24 VDC, with 15 m connection cable, II 2G Ex mb IIC T6 Gb/II 2D Ex mb IIIC T85°C Db, LE 07016040156-15

Accessories

DescriptionPart No.
Fuse 5 x 20, semi-timelag, 200 mA040586
Fuse carrier with bayonet catch040587
Fuse carrier040588

Similar products

ATEX Electromagnet

ATEX-proof electromagnet

For use exclusively in hazardous zones 2 & 22

ATEX Electromagnet

ATEX-proof electromagnets

Encapsulated, with connection terminal box, for hazardous zones 1 & 2, 21 & 22