Hand switch

For surface & flush installation on hold-open systems

Characteristics

  • According to fire protection standard EN 14637, a manual release button is required for hold-open systems for fire and smoke closures
  • Pressing the button releases a fire or a smoke door
  • The push-button surface must be red and have the inscription “close door” or similar
  • Must be clearly visible and easy to operate
  • Must be in the immediate vicinity of the closure and must not be covered by the open door
  • It is recommended to install it at a height of approx. 1.40 m +/- 0.2 m above the floor

Product details

Versions

Handtaster Feststellanlagen Aufputz

Surface installation

Handtaster Feststellanlagen Unterputz
Flush installation

Dimensions

All dimensions in mm

Hand switch for surface installation

Part no. 040005

Surface hand-switch for hold-open system - dimensions

Hand switch for flush installation

Part no. 040053

Flush hand-switch for hold-open system - dimensions

Installation

Installation

Important: When installed, the hand switch must not be hidden by the open door and must be freely accessible.

Order information

Order Information

DescriptionPart No.
Emergency hand switch, flush mounting040053
Emergency hand switch, surface type, red rocker040005

Downloads

File NameType
Documents
Catalog: Accessories for hold-open systemspdf